Branch Model: SIMPLEOC1

 

Model Equations and/or Block Diagrams   

Is the same as the TIOCRS with the IEEE C37.112-1996 standard used for the relay modeling.

Parameters:

ThresholdMult Multiplier on limit to determine threshold current; set to 1 for threshold to match limit
Tdm Time Dial Multiplier
Treset Time to reset if the current is zero, in seconds
P Curve Exponent Parameter. See more information with paramters A, B
A Curve Coefficient A. Usage depends on Curve Type. Let M = (I/Ithres). Then IEEE curves use Tdm*{B + A/(M^p - 1)}
B Curve Coefficient B. Usage depends on Curve Type. Let M = (I/Ithres). Then IEEE curves use Tdm*{B + A/(M^p - 1)}